12kV / 24kV PT Trolley
Parameter Téknis
No. | Barang | Unit | Data |
1 | Tegangan dipeunteun (Ur) | V | 12/24 |
2 | tegangan tinggi ayeuna sekering (lr) | A | 3.15A |
3 | Kapasitas dipeunteun trafo | kVA | 3~5 |
4 | Tegangan tahan waktos pondok dipeunteun (Ud) | kV | 50 |
5 | Dipeunteun dorongan kilat tahan tegangan (Kaluhur) | kV | 125 |
6 | Kahirupan mékanis | Kelas | M1/M2 |
7 | Isolasi status cart sareng modul komunikasi indikasi posisi Modous (RS485) | - | Pilihan |
8 | Modul operasi listrik | - | Pilihan |
Ukuran 12 kV
Dipeunteun ayeuna | P | A | B | C | D | E |
630A | 150 | 502 | 532 | 490 | 202 | 100 |
210 | 652 | 682 | 638 | 277 | 160 | |
275 | 852 | 882 | 838 | 377 | 200 |
Diménsi 24kV (Pikeun kabinét 1000 rubak)
Diménsi 24kV (Pikeun kabinét 800 rubak)
12Kv / 24kV Isolating Trolley (Busbar Trolley, Disconnecting Trolley)
Aplikasi
The 24kV withdrawable trolley terasing boga ciri desain sampurna, struktur kompak, operasi gampang jeung kinerja alus teuing.Produkna saluyu sareng IEC62271-102 "Switchgear tegangan luhur sareng alat kontrol - Bagian 102 Pemutus AC sareng saklar grounding".Cocog jeung tegangan tinggi cabinets sentral, cocog pikeun hawa-insulated indoor withdrawable switch sentral cabinets, pikeun sirkuit utama bisa switched dina kaayaan no-beban, jeung circuit breaker keur repaired nungguan isolasi listrik pakakas listrik tina garis hirup. alat interlocking aman jeung panto.
Parameter Téknis
No. | Barang | Unit | Data |
1 | Tegangan dipeunteun (Ur) | V | 12/24 |
2 | Dipeunteun ayeuna (lr) | A | 630/1250 |
3 | Dipeunteun pondok-waktos tahan ayeuna (lk) | kA | 25 |
4 | Dipeunteun lila-circuit pondok (tk) | s | 3 |
5 | Dipeunteun arus puncak circuit pondok (lp) | kA | 65 |
6 | Tegangan tahan waktos pondok dipeunteun (Ud) | kV | 50 |
7 | Dipeunteun dorongan kilat tahan tegangan (Kaluhur) | kV | 125 |
8 | Kahirupan mékanis | Kelas | M1/M2 |
9 | Status keretas tangan isolasi sareng modul komunikasi indikasi posisi Modous (RS485) | - | Pilihan |
10 | Modul operasi listrik | - | Pilihan |